Characteristic | LSZH |
---|---|
Operating Temp | -40°C to +70°C |
Storage Temp | -40°C to +70°C |
Install Temp | -20°C to +60°C |
Flame Retardancy | OFC-ST1, ABS type approved 23-2436207 |
Crush Resist | 1800 N/cm (TIA-455-41) |
Flex Resist | 2000 cycles (TIA-455-104) |
Jacket Type | Z |
OCC D-Series Distribution – Low-Smoke Zero-Halogen Braided-Armor ABS-approved cables meet the functional requirements of the following standards:
Tensile Load | Minimum Bend Radius | ||||||||
---|---|---|---|---|---|---|---|---|---|
Fiber Count | Part Number | Part Number Configurator | Diameter mm (in) |
Weight kg/km (lbs/1,000ft) |
Installation N (lbs) |
Operation N (lbs) |
Installation cm (in) |
Longer Term cm (in) |
|
2 | Please Call OCC for ordering assistance. |
9.3 (0.37) |
126.0 (85.0) |
1,400 (310) |
450 (100) |
14.0 (5.5) |
9.3 (3.7) |
||
4 | Please Call OCC for ordering assistance. |
9.5 (0.37) |
132.0 (89.0) |
1,400 (310) |
450 (100) |
14.3 (5.6) |
9.5 (3.7) |
||
6 | Please Call OCC for ordering assistance. |
9.9 (0.39) |
144.0 (97.0) |
1,400 (310) |
450 (100) |
14.9 (5.9) |
9.9 (3.9) |
||
8 | Please Call OCC for ordering assistance. |
10.4 (0.41) |
158.0 (106.0) |
1,600 (360) |
525 (120) |
15.6 (6.1) |
10.4 (4.1) |
||
10 | Please Call OCC for ordering assistance. |
10.8 (0.43) |
171.0 (115.0) |
1,800 (400) |
600 (135) |
16.2 (6.4) |
10.8 (4.3) |
||
12 | Please Call OCC for ordering assistance. |
11.5 (0.45) |
193.0 (130.0) |
2,700 (600) |
600 (135) |
17.3 (6.8) |
11.5 (4.5) |
||
18 | Please Call OCC for ordering assistance. |
11.5 (0.45) |
190.0 (128.0) |
2,700 (600) |
600 (135) |
17.3 (6.8) |
11.5 (4.5) |
||
24 | Please Call OCC for ordering assistance. |
13.1 (0.52) |
237.0 (159.0) |
3,000 (670) |
1,000 (220) |
19.7 (7.8) |
13.1 (5.2) |
Please Login Here to access additional documents.